12
Troubleshooting
The StatStation will report System Alerts for problems with your generator and standby system and the LED will flash red. An
audible alarm will accompany Generator and Standby System Alerts.
System Alert Mode – Generator Faults
System Alert Display Fault Cause Fault Remedy
Low Battery Voltage 1. Generator battery is low. 1. Recharge or replace generator
battery.
Low Oil Pressure 1. Engine oil level is low. 1. Add oil to full mark on dipstick.
2. Engine oil leaks. 2. Contact authorized service center.
Low Voltage 1. Generator circuit breaker open. 1. Close generator circuit breaker.
2. Fault in generator. 2. Contact authorized service center.
3. Fault in connection. 3. Contact authorized service center.
4. Insufficient fuel supply. 4. Check fuel delivery system. Contact
authorized service center.
5. Clogged air filter. 5. Clean or replace air filter.
Engine Fails to Start 1. Insufficient fuel supply. 1. Check fuel delivery system. Contact
authorized service center.
2. Faulty spark plugs. 2. Check spark plug.
3. Clogged air filter. 3. Clean or replace air filter.
4. Faulty engine ignition. 4. Contact authorized service center.
Low Frequency 1. Fault in generator. 1. Contact authorized service center.
2. Fault in connection. 2. Contact authorized service center.
3. Insufficient fuel supply. 3. Check fuel delivery system. Contact
authorized service center.
4. Clogged air filter. 4. Clean or replace air filter.
Engine Overspeed 1. Failed engine governor. 1. Contact authorized service center.
High Oil Temperature 1. Generator access doors removed
while running.
1. Install generator access doors.
2. Obstructed cooling air inlet screens. 2. Check and clean generator cooling air
inlet or exhaust port.
3. Clogged engine cooling fins. 3. Contact authorized service center.
4. Faulty temperature switch/wiring. 4. Contact authorized service center.