Humidification System
21 69-2307—01
No. of
Red
Light
Blinks
Fault Description Auto-
Recoverable?
Steps to Fix
To be Performed by Professional HVAC Technician Only
8–11 The backup weld
monitor input is active
when the backup
heater relay is off.
No •Replacetheunit.
12 Temperature of the
electronic circuit
board is too high.
Yes,systemwill
return to “Ready”
if fault no longer
exists in 1 hour.
•Ensureventilationholesinthecoverareclearof
obstruction, and that 1 foot of clearance is maintained
around the cover’s vent holes.
• Ensurethehumidifierisinstalledinalocationwith
conditioned air 32°F (0°C) to 104°F (40°C).
• Turnhumidistatoffandallowtimeforelectronicboardtocool.
• TurnhumidistatonandpressRESETbutton.
• ConfirmhumiditycallstartsbyHUMIDIFYINGlightturningon.
• Allowunittorunandcheckforsteamleaksaroundtankand
ventilation holes.
• Ifsteamispresent,replacethehumidifier.
13 Tank failed to drain. No •Waterintankmaybehot(>140ºF[60ºC]).
•PresstheEMPTYbutton.
•Ifunitfailstodrain,waitforwaterintanktocool.Ensure
tank water is cool before proceeding.
• Oncecool,followtankcleaningsteps(pages23–25).
• ReassembletankandpresstheRESETbutton.
• Iffaultpersists,replacethesolenoidvalve.
14 Heater failed to boil
water.
Yes,systemwill
return to “Ready”
if fault no longer
exists in 1 hour.
• Followtankcleaningsteps(pages23–25).
• ReassembletankandpresstheRESETbutton.
• Iffaultreturns,replacetheheatingelementwiththe
applicable wattage replacement part.
15 No Airflow. Yes •EnsureDifferentialPressureSwitchisinstalledandwired
correctly. See the Wiring section for proper wiring.
•EnsureDIPswitchesaresetcorrectly.
•Iffaultpersists,replaceAFSand/orunit.