8 Rheem Heating, Cooling and Water Heating
External Static Pressure-Inches W.C. [kPa]
X-13 CFM wet coil with filter and heaters
RPM 1120
Blower Size/
Motor
HP [W]
# of Speeds
1132
Motor
Speed
1136
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Motor
Speed
From
Factory
1141 1146 1153 1160
Watts 294 271 266 257 239 231 214
10x6
1/3 HP [249]
2 Speed
Dual Voltage
CFM 811 [383] 785 [370] 759 [358] 726 [343] 708 [334]
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
982 1008 1026 1050 1081
RPM 1020 1035 1068 1095 1119 1138 1147
Nominal
Cooling
Capacity
Tons
2
2.5
3
1.5
Watts 198 207 206 204 211 205 189
10x6
1/3 HP [249]
2 Speed
Dual Voltage
4
977/708 CFM
[461/334 L/s]
CFM 599 [283] 578 [273] 544 [257] 509 [240] 474 [224]
5
CFM 977 [461] 930 [439] 898 [424] 850 [401]
RPM 832 875 905 935 963
801 [378] 746 [352] 687 [324]
Watts 177 186 182 188 189
RPM 886 921 958 986 1022 1053 1083
Watts 267 275 287 290 301 305 315
10x8
1/2 HP [373]
2 Speed
Dual Voltage
CFM 1053 [497] 1003 [473] 969 [457] 928 [438] 897 [423]
RPM 835 864 903 933 973
2
1170/897 CFM
[552/423 L/s]
5
CFM 1170 [552] 1127 [532] 1085 [512] 1048 [495] 1012 [478] 973 [459] 943 [445]
Watts
212 216 227 232 242
RPM 974 1006 1036 1063 1098 1120 1131
Watts 365 378 383 390 399 393 377
10x8
1/2 HP [373]
2 Speed
Dual Voltage
CFM 1208 [570] 1172 [553] 1125 [531] 1087 [513] 1049 [495]
RPM 906 938 968 1002 1030
5
1316/1049 CFM
[621/495 L/s]
5
CFM 1316 [621] 1275 [602] 1229 [580] 1191 [562] 1151 [543] 1093 [516] 1039 [490]
Watts 284 299 306 315 322
2
827/474 CFM
[390/224 L/s]
5
CFM 827 [390] 804 [379] 779 [368] 740 [349] 708 [334] 659 [311] 608 [287]
Watts
95 96 108 102 112
3
4
5
3
5
5
5
5
208V/240V Airflow Performance Data—RHBL (X-13 (ECM) Motor)
Notes: X-13 motor speed changes.
All X-13 motors have 5 speed taps. Speed tap 1 is for continuous fan. Speed tap 2 (low static) and speed tap 3 (high static) are for lower tonnage. Speed tap
4 (low static) and speed tap 5 (high static) are for higher tonnage.
X-13 air handlers are always shipped from factory at speed tap 5. To change to 1.5-ton or 2.5-ton airflow, move the blue wire to speed tap 2 or 3 on the
X-13 motor. The low static speed tap 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5" WC. The high static speed tap 3 (lower
tonnage) and 5 (higher tonnage) are used for external static exceeding 0.5" WC. Move the blue wire to the appropriate speed tap as required by the
application needs.
• The airflow for continuous fan (speed tap 1) is 50% of the speed tap 4 airflow.
• The above airflow table lists the airflow information for air handlers with maximum heater allowed for each model.
[ ] Designates Metric Conversions