INSTALLATION INSTRUCTIONS
PACKAGE AIR CONDITIONERS
RSNM/RSPM SERIES — (2.0 - 5.0 TONS) FEATURING
NEW INDUSTRY STANDARD R-410A REFRIGERANT:
92-21354-58-05
SUPERSEDES 92-21354-58-04
!
WARNING
!
THESE INSTRUCTIONS ARE INENDED AS AN AID TO
QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER
INSTALLATION, ADJUSTMENT AND OPERATION OF THIS
UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE
ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO
FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER
INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE
POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ISO 9001:2008
(14 SEER ONLY)
Vista de pagina 0
1 2 3 4 5 6 ... 43 44

Indice de contenidos

Pagina 1 - INSTALLATION INSTRUCTIONS

[ ] INDICATES METRIC CONVERSIONINSTALLATION INSTRUCTIONSPACKAGE AIR CONDITIONERSRSNM/RSPM SERIES — (2.0 - 5.0 TONS) FEATURINGNEW INDUSTRY STANDARD R-4

Pagina 2 - TABLE OF CONTENTS

VIII.FILTERSFilters are not provided with this unit. They must be supplied and installed in the returnair duct by the installer. A field installed fil

Pagina 3 - I. SAFETY INFORMATION

11B. POWER WIRING AND ELECTRIC HEATER KIT INSTRUCTIONS1. Turn off power to unit.2. Remove control box access panel.3. Remove unit indoor section top c

Pagina 4 - V. SPECIFICATIONS

12D. INTERNAL WIRING1. A diagram of the internal wiring of this unit is located on the electrical control boxcover. If any of the original wire as sup

Pagina 5 - /8" [22.2 mm]

13INDOOR AIRFLOW PERFORMANCE - RSNM - 230 VOLTSCFM Air Delivery/RPM/Watts-230 VoltsExternal Static Pressure-Inches W.C.0.10 0.20 0.30 0.40 0.50 0.60 0

Pagina 6 - ROUND DUCT CONNECTIONS

14INDOOR AIRFLOW PERFORMANCE - RSNM - 208 VOLTSCFM Air Delivery/RPM/Watts-208 VoltsExternal Static Pressure-Inches W.C.0.10 0.20 0.30 0.40 0.50 0.60 0

Pagina 7

15INDOOR AIRFLOW PERFORMANCE - RSPM - 230 VOLTSCFM Air Delivery/RPM/Watts-230 VoltsExternal Static Pressure-Inches W.C.0.10 0.20 0.30 0.40 0.50 0.60 0

Pagina 8 - VI. INSTALLATION

16INDOOR AIRFLOW PERFORMANCE - RSPM - 208 VOLTSCFM Air Delivery/RPM/Watts-208 VoltsExternal Static Pressure-Inches W.C.0.10 0.20 0.30 0.40 0.50 0.60 0

Pagina 9 - VII.DUCTWORK

17XII. PRE-START CHECK1. Is unit properly located and level?2. Is ductwork insulated, weatherproofed, with proper spacing to combustible materi-als?3.

Pagina 10 - X. ELECTRICAL WIRING

18J. Current at Contactor _______________________AmpsK. Model Number_________________________________L. Serial Number ________________________________

Pagina 11 - C. CONTROL WIRING (Class II)

19Model RSNM- Series A024JK A030JK A036CK A036JKCooling Performance1Continued -> Gross Cooling Capacity Btu [kW] 24,800 [7.27] 30,000 [8.79] 37,20

Pagina 12 - XI. INDOOR AIR FLOW DATA

2TABLE OF CONTENTSI. Safety Information ...3II. Introduc

Pagina 13

20GENERAL DATA - RSNMNOMINAL SIZES 2-5 TONS [7-17.6 kW]Model RSNM- Series A042CK A042JK A048CK A048JKCooling Performance1Continued -> Gross Coolin

Pagina 14

21GENERAL DATA - RSNMNOMINAL SIZES 2-5 TONS [7-17.6 kW]Model RSNM- Series A060CK A060JKCooling Performance1Gross Cooling Capacity Btu [kW] 63,000 [18.

Pagina 15

22Model RSPM- Series A024JKA030JKA036CKA036JKCooling Performance1Continued -> Gross Cooling Capacity Btu [kW] 25,200 [7.38] 30,400 [8.91] 37,600 [

Pagina 16

23GENERAL DATA - RSPMNOMINAL SIZES 2-5 TONS [7-17.6 kW][ ] Designates Metric ConversionsNOTES:1. Cooling Performance is rated at 95°F ambient, 80°F en

Pagina 17 - XIII. STARTUP

24[ ] Designates Metric ConversionsNOTES:1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capaci

Pagina 18 - XIV.OPERATION

25XVI. MISCELLANEOUSELECTRICAL DATA-A024JK -A030JK -A036CK -A036JK -A042CK -A042JK -A048CK -A048JK -A060CK -A060JKUnit Operating Voltage Range

Pagina 19 - XV. GENERAL DATA - RSNM

26ELECTRICAL DATA - continued187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253208/230 208/23023/23 24/24

Pagina 20 - GENERAL DATA - RSNM

27208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILLARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATIONSingle Power Supply For Both Unit And Heater Kit Se

Pagina 21

28208-240 VOLT, THREE PHASE, 60 HZ, AUXILLARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATIONSingle Power Supply For Both Unit And Heater Kit Sep

Pagina 22 - GENERAL DATA - RSPM

29AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RSPM208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILLARY ELECTRIC HEATER KITS CHARACTERISTI

Pagina 23

3I. SAFETY INFORMATION!WARNINGPROPOSITION 65: THIS APPLIANCE CONTAINS FIBERGLASS INSULATION.RESPIRABLE PARTICLES OF FIBERGLASS ARE KNOWN TO THE STATE

Pagina 24

30208-240 VOLT, THREE PHASE, 60 HZ, AUXILLARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATIONSingle Power Supply For Both Unit And Heater Kit Sep

Pagina 25 - ELECTRICAL DATA

31FIGURE 7WIRING DIAGRAM – RSNM

Pagina 26 - ELECTRICAL DATA - continued

32FIGURE 8WIRING DIAGRAM – RSNM

Pagina 27

33FIGURE 9WIRING DIAGRAM – RSPM – WITH X-13 BLOWER MOTOR

Pagina 28

34FIGURE 10WIRING DIAGRAM – RSPM – WITH X-13 BLOWER MOTOR

Pagina 29

35FIGURE 11WIRING DIAGRAM

Pagina 30

36FIGURE 12WIRING DIAGRAM

Pagina 31 - FIGURE 7

37FIGURE 132TON AIR CHARGING CHART

Pagina 32 - FIGURE 8

38FIGURE 142.5 TON AIR CHARGING CHART

Pagina 33 - FIGURE 9

39FIGURE 153.0 TON CHARGING CHART

Pagina 34 - FIGURE 10

4II. INTRODUCTIONThis booklet contains the installation and operating instructions for your self-containedair conditioner. There are a few precautions

Pagina 35 - FIGURE 11

40FIGURE 163.5 TON CHARGING CHART

Pagina 36 - FIGURE 12

41FIGURE 174.0 TON CHARGING CHART

Pagina 37 - FIGURE 13

42FIGURE 185.0 TON CHARGING CHART92-102337-06 -00OUTDOOR AMBIENT (°F DB)55657585951051155 TON COOLING - 13 AND 14 SEERSYSTEM CHARGE CHART - REFRIGERAN

Pagina 38 - FIGURE 14

43SYMPTOM POSSIBLE CAUSE REMEDYUnit will not run • Power off or loose electrical connection • Check for correct voltage at compressor contactor in con

Pagina 40 - FIGURE 16

5FIGURE 1UNIT DIMENSIONS AND ACCESS LOCATIONSModel024, 030, 036042, 048, 060Height “A”29 1/8"37 1/8"024, 030, 036, 042, 043048, 060211/16&qu

Pagina 41 - FIGURE 17

6DUCT CONNECTIONSSQUARE DUCT CONNECTIONS14.00"[355.6 mm]14.00"[355.6 mm][19.05 mm]"34/14.00"[355.6 mm]14.00"[355.6 mm][19.05

Pagina 42 - OUTDOOR AMBIENT (°F DB)

7A. GENERALThe Packaged Air Conditioner is available without heat or with 5, 7, 10, 15, or 20 kWelectric heat. Cooling capacities of 2, 21⁄2, 3, 31⁄2

Pagina 43 - TROUBLE SHOOTING CHART

8Recovery Cylinders:-400 PSIG Pressure Rating-Dept. of Transportation 4BA400 or BW400VI. INSTALLATIONA. GENERAL1. PRE-INSTALLATION CHECK-POINTSBefore

Pagina 44

93. The location of the unit on the roof should be such as to provide proper access forinspection and servicing (Figure 3).IMPORTANT: If unit will not