[ ] INDICATES METRIC CONVERSIONINSTALLATION INSTRUCTIONSPACKAGE AIR CONDITIONERSRSNM/RSPM SERIES — (2.0 - 5.0 TONS) FEATURINGNEW INDUSTRY STANDARD R-4
VIII.FILTERSFilters are not provided with this unit. They must be supplied and installed in the returnair duct by the installer. A field installed fil
11B. POWER WIRING AND ELECTRIC HEATER KIT INSTRUCTIONS1. Turn off power to unit.2. Remove control box access panel.3. Remove unit indoor section top c
12D. INTERNAL WIRING1. A diagram of the internal wiring of this unit is located on the electrical control boxcover. If any of the original wire as sup
13INDOOR AIRFLOW PERFORMANCE - RSNM - 230 VOLTSCFM Air Delivery/RPM/Watts-230 VoltsExternal Static Pressure-Inches W.C.0.10 0.20 0.30 0.40 0.50 0.60 0
14INDOOR AIRFLOW PERFORMANCE - RSNM - 208 VOLTSCFM Air Delivery/RPM/Watts-208 VoltsExternal Static Pressure-Inches W.C.0.10 0.20 0.30 0.40 0.50 0.60 0
15INDOOR AIRFLOW PERFORMANCE - RSPM - 230 VOLTSCFM Air Delivery/RPM/Watts-230 VoltsExternal Static Pressure-Inches W.C.0.10 0.20 0.30 0.40 0.50 0.60 0
16INDOOR AIRFLOW PERFORMANCE - RSPM - 208 VOLTSCFM Air Delivery/RPM/Watts-208 VoltsExternal Static Pressure-Inches W.C.0.10 0.20 0.30 0.40 0.50 0.60 0
17XII. PRE-START CHECK1. Is unit properly located and level?2. Is ductwork insulated, weatherproofed, with proper spacing to combustible materi-als?3.
18J. Current at Contactor _______________________AmpsK. Model Number_________________________________L. Serial Number ________________________________
19Model RSNM- Series A024JK A030JK A036CK A036JKCooling Performance1Continued -> Gross Cooling Capacity Btu [kW] 24,800 [7.27] 30,000 [8.79] 37,20
2TABLE OF CONTENTSI. Safety Information ...3II. Introduc
20GENERAL DATA - RSNMNOMINAL SIZES 2-5 TONS [7-17.6 kW]Model RSNM- Series A042CK A042JK A048CK A048JKCooling Performance1Continued -> Gross Coolin
21GENERAL DATA - RSNMNOMINAL SIZES 2-5 TONS [7-17.6 kW]Model RSNM- Series A060CK A060JKCooling Performance1Gross Cooling Capacity Btu [kW] 63,000 [18.
22Model RSPM- Series A024JKA030JKA036CKA036JKCooling Performance1Continued -> Gross Cooling Capacity Btu [kW] 25,200 [7.38] 30,400 [8.91] 37,600 [
23GENERAL DATA - RSPMNOMINAL SIZES 2-5 TONS [7-17.6 kW][ ] Designates Metric ConversionsNOTES:1. Cooling Performance is rated at 95°F ambient, 80°F en
24[ ] Designates Metric ConversionsNOTES:1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capaci
25XVI. MISCELLANEOUSELECTRICAL DATA-A024JK -A030JK -A036CK -A036JK -A042CK -A042JK -A048CK -A048JK -A060CK -A060JKUnit Operating Voltage Range
26ELECTRICAL DATA - continued187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253208/230 208/23023/23 24/24
27208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILLARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATIONSingle Power Supply For Both Unit And Heater Kit Se
28208-240 VOLT, THREE PHASE, 60 HZ, AUXILLARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATIONSingle Power Supply For Both Unit And Heater Kit Sep
29AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RSPM208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILLARY ELECTRIC HEATER KITS CHARACTERISTI
3I. SAFETY INFORMATION!WARNINGPROPOSITION 65: THIS APPLIANCE CONTAINS FIBERGLASS INSULATION.RESPIRABLE PARTICLES OF FIBERGLASS ARE KNOWN TO THE STATE
30208-240 VOLT, THREE PHASE, 60 HZ, AUXILLARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATIONSingle Power Supply For Both Unit And Heater Kit Sep
31FIGURE 7WIRING DIAGRAM – RSNM
32FIGURE 8WIRING DIAGRAM – RSNM
33FIGURE 9WIRING DIAGRAM – RSPM – WITH X-13 BLOWER MOTOR
34FIGURE 10WIRING DIAGRAM – RSPM – WITH X-13 BLOWER MOTOR
35FIGURE 11WIRING DIAGRAM
36FIGURE 12WIRING DIAGRAM
37FIGURE 132TON AIR CHARGING CHART
38FIGURE 142.5 TON AIR CHARGING CHART
39FIGURE 153.0 TON CHARGING CHART
4II. INTRODUCTIONThis booklet contains the installation and operating instructions for your self-containedair conditioner. There are a few precautions
40FIGURE 163.5 TON CHARGING CHART
41FIGURE 174.0 TON CHARGING CHART
42FIGURE 185.0 TON CHARGING CHART92-102337-06 -00OUTDOOR AMBIENT (°F DB)55657585951051155 TON COOLING - 13 AND 14 SEERSYSTEM CHARGE CHART - REFRIGERAN
43SYMPTOM POSSIBLE CAUSE REMEDYUnit will not run • Power off or loose electrical connection • Check for correct voltage at compressor contactor in con
44CM 0510
5FIGURE 1UNIT DIMENSIONS AND ACCESS LOCATIONSModel024, 030, 036042, 048, 060Height “A”29 1/8"37 1/8"024, 030, 036, 042, 043048, 060211/16&qu
6DUCT CONNECTIONSSQUARE DUCT CONNECTIONS14.00"[355.6 mm]14.00"[355.6 mm][19.05 mm]"34/14.00"[355.6 mm]14.00"[355.6 mm][19.05
7A. GENERALThe Packaged Air Conditioner is available without heat or with 5, 7, 10, 15, or 20 kWelectric heat. Cooling capacities of 2, 21⁄2, 3, 31⁄2
8Recovery Cylinders:-400 PSIG Pressure Rating-Dept. of Transportation 4BA400 or BW400VI. INSTALLATIONA. GENERAL1. PRE-INSTALLATION CHECK-POINTSBefore
93. The location of the unit on the roof should be such as to provide proper access forinspection and servicing (Figure 3).IMPORTANT: If unit will not