Pagina 1 - INSTALLATION INSTRUCTIONS

92-101691-02-06SUPERSEDES 92-101691-02-05AIR-COOLED CONDENSING UNITS(-)ARL-JEZ 16 SEER AND (-)ASL-JEZ 18 SEER MODELSEQUIPPED WITH THE INTEGRATED COMFO

Pagina 2 - TABLE OF CONTENTS

10TUBING INSTALLATIONObserve the following when installing correctly sized type “L” refrigerant tubingbetween the condensing unit and evaporator coil:

Pagina 3 - UNIT MODEL NUMBER EXPLANATION

11TABLE 2SUCTION LINE LENGTH SIZE VS. CAPACITY MULTIPLIER (2-STAGE R-410A)2 Ton3/4" I.D. 3/4" I.D. 7/8" I.D. 7/8" I.D.4 Ton5 TonUn

Pagina 4 - CORROSIVE ENVIRONMENT

12TABLE 4LIQUID LINE SIZING (2-STAGE R-410A)Liquid Line SizeOutdoor unit above Indoor Coil (Cooling Only)Total Equivalent Length - Feet25 50 75 100 12

Pagina 5 - LOCATING UNIT

13EVACUATION PROCEDUREEvacuation is the most important part of the entire service procedure. The life andefficiency of the equipment is dependent upon

Pagina 6 - UNIT MOUNTING

14CHECKING REFRIGERANT CHARGECharge for all systems should be checked against the Charging Chart inside theaccess panel cover. Before using the chart,

Pagina 7 - SERVICING R-410A MODELS

15CHARGING BY WEIGHTFor a new installation, evacuation of interconnecting tubing and evaporator coil isadequate; otherwise, evacuate the entire system

Pagina 8 - EVAPORATOR COIL

16CONTROL WIRING(See Figure 2)If the low voltage control wiring is run in conduit with the power supply, Class I insu-lation is required. Class II ins

Pagina 9 - INTERCONNECTING TUBING

17FACTORY INSTALLED ACCESSORIESHARD START COMPONENTSStart components are factory installed.HIGH AND LOW PRESSURE CONTROLS(HPC OR LPC)Pressure controls

Pagina 10 - TUBING CONNECTIONS

18FIELD INSTALLED ACCESSORIESCOMPRESSOR CRANKCASE HEAT (CCH)While scroll compressors usually do not require crankcase heaters, there areinstances when

Pagina 11 - LEAK TESTING

19CONTROL DESCRIPTION (SEE FIGURE 3)7-Segment LED• Displays status and diagnostic codes (See Status and Diagnostic Description)• Displays diagnostic/f

Pagina 12

2TABLE OF CONTENTSChecking Product Received . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2Dimensions . . . . . . . . . .

Pagina 13 - CHECKING AIRFLOW

20Low Volt Fuse• If required replace with 3 A automotive ATC style blade fuseLow Pressure Control (LPC Input – E14)• Low-pressure control is factory i

Pagina 14 - CHECKING REFRIGERANT CHARGE

217 -Segment Display Code Diagnostic Description Status / Possible Cause -Troubleshooting Information 0 Standby Standby - No call for operation c Y

Pagina 15 - ELECTRICAL WIRING

22(*) – Indicates flash code will be an output on the ICC “L” terminal to the indoorthermostat “L” terminal. Unless a diagnostic/fault is manually cle

Pagina 16 - CONTROL WIRING

23GENERAL SERVICE ANALYZER CHARTSCOMPRESSOR OVERHEATINGSYMPTOMS POSSIBLE CAUSE CHECK/REMEDIESHigh superheat Low charge Check system chargeFaulty meter

Pagina 17 - FACTORY INSTALLED ACCESSORIES

24SYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIESShort cycling of compressor (cont.) Low charge Check system chargeLow evaporator air flow Dirty coilDirty f

Pagina 18 - COMFORT CONTROL SYSTEM

25LOSS OF LUBRICATIONSYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIESCompressor failures Line tubing too long Add oil to the recommended levelLine tubing too

Pagina 19 - FIGURE 3

26THERMOSTATIC EXPANSION VALVESSYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIESHigh Superheat, Low Suction Pressure Moisture freezing and blocking valve Reco

Pagina 20

27THERMOSTATIC EXPANSION VALVESSYMPTOMS POSSIBLE CAUSE CHECK OR REMEDIESSuperheat is low to normal Unequal evaporator circuit loading Ensure air flow

Pagina 21 - (2-stage unit only)

28Caution – UNIT MAY START SUDDENLY AND WITHOUT WARNING S ol i d red L E D li ght i ndicates a thermostat cal l for uni t operation i s present at t

Pagina 22 - SINGLE-POLE COMPRESSOR RELAY

29TROUBLE SHOOTINGIn diagnosing common faults in the air conditioning system, it is useful to presentthe logical pattern of thought that is used by ex

Pagina 23 - COMPRESSOR OVERHEATING

3FIGURE 1DIMENSIONS AND INSTALLATION CLEARANCESUNIT MODEL NUMBER EXPLANATION(-)ARL – 036 JEZZ-SCROLL COMPRESSORE = EQUIPPED WITH THECOMFORT CONTROL SY

Pagina 24 - CONTAMINATION

30MECHANICAL CHECKS FLOW CHARTUnit Running?YESLow Head PressureLow Suction PressureOpen IPR Valve Dirty EvaporatorInadequate AirflowRestricted Filter-

Pagina 25 - FLOODING

SYSTEM CHARGE TROUBLESHOOTINGSUPERHEAT CALCULATION1. Measure the suction pressure at the suction line service valve.2. Convert the suction pressure to

Pagina 26 - THERMOSTATIC EXPANSION VALVES

32SYMPTOM POSSIBLE CAUSE REMEDYUnit will not run • Power off or loose electrical connection • Check for correct voltage at contactor in condensing uni

Pagina 27

33FIGURE 5(-)ARL, -024, -036, -048 WIRING DIAGRAM

Pagina 28 - FIGURE 4

34FIGURE 6(-)ARL-060 JEZ, (-)ASL-024 JEZ, (-)ASL-036 JEZ WIRING DIAGRAM

Pagina 31 - SYSTEM CHARGE TROUBLESHOOTING

4GENERALThe information contained in this manual has been prepared to assist in the properinstallation, operation and maintenance of the air condition

Pagina 32 - TROUBLE SHOOTING CHART

5• Frequent washing of the cabinet, fan blade and coil with fresh water will removemost of the salt or other contaminants that build up on the unit.•

Pagina 33 - FIGURE 5

6CUSTOMER SATISFACTION ISSUES• The condenser should be located away from the living, sleeping and recreation-al spaces of the owner and those spaces o

Pagina 34 - FIGURE 6

7REFRIGERANT CONNECTIONSAll units are factory charged with Refrigerant R-410A. All models are supplied withservice valves. Keep tube ends sealed until

Pagina 35

8SPECIFICATION OF R-410A:Application: R-410A is not a drop-in replacement for R-22; equipment designsmust accommodate its higher pressures. It cannot

Pagina 36

9The thermostatic expansion valve is specifically designed to operate with R-410A.DO NOT use an R-22 TXV or evaporator. The existing evaporator must b