INTELLI-VENT TROUBLESHOOTING GUIDE
Technical Training Department Ashland City, Tennessee © 2005
14 of 24
ERROR CODE 11 - HIGH TEMPERATURE CUTOFF (ECO) ACTIVATED
Water temperature in the tank exceeded 195°F and activated the ECO.
Check / Repair:
Turn the power off for 10-20 seconds and then on again to clear this error code.
Residential control - replace the control if the error code cannot be cleared.
Commercial control - cool water temperature below 120°F, cycle power off and on
to reset control. Replace the control if the error code persists.
ERROR CODE 12 - TEMPERATURE ADJUST BUTTONS STUCK CLOSED
The self diagnostic check detected a temperature adjust button stuck closed.
Check / Repair:
Make sure no objects are leaning against the front of the control.
Lightly press and release each of the buttons once.
If the above actions do not clear the error, the control will continue to regulate
water temperature at the last setting, but you will not be able to change settings
unless you replace the Intelli-Vent™ control.
ERROR CODE 13 - TEMPERATURE PROBE OPEN OR SHORTED
The self diagnostic test has detected the water temperature sensor (thermistor) is either
open or short circuited.
Check / Repair:
Turn the power off for 10-20 seconds then on again to clear this error code.
This part of the control cannot be replaced or serviced. If the error code cannot be
cleared, the Intelli-Vent™ control must be replaced.