Rheem R-410A Manual de usuario Pagina 7

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 36
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 6
7
REFRIGERANT CONNECTIONS
All units are factory charged with Refrigerant R-410A. All models are supplied with
service valves. Keep tube ends sealed until connection is to be made to prevent
system contamination.
TOOLS REQUIRED FOR INSTALLING &
SERVICING R-410A MODELS
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use
R-22 service equipment or components on R-410A equipment.
Vista de pagina 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 35 36

Comentarios a estos manuales

Sin comentarios