Low Volt Fuse
If required replace with 3 A automotive ATC style blade fuse
Low Pressure Control (LPC Input E14)
Low-pressure control is factory installed
Low pressure control is an automatic resetting device
High Pressure Control (HPC Input E14)
High-pressure control is factory installed
High pressure control is an automatic resetting device
Compressor Solenoid Output (E14)
Compressor solenoid output is controlled by the control for second stage cooling
operation.
Ambient Temperature Sensor
Included on control but not required in the cooling only condenser application
TEST and SW2 Buttons
TEST and SW2 buttons used to enter Test and Fault Recall Mode
ICC CONTROL OPERATION
Installation Verification
24V AC power on R and C must be present at the ICC for it to operate
Line voltage must be present at the ICC for the compressor and the outdoor fan
to operate
When line and 24VAC control voltage is present and there is no Y1 call, or other
diagnostics displayed, the control will display an “O” for standby mode
If a Y1 call is initiated within 3 minutes of unit power-up or last compressor activa-
tion the control will display a flashing “c” and the red Led will activate to solid on
Call for Operation (Y1 Call)
The ICC has an on/off fan delay of one (1) second.
The ICC ignores state of LPC for 90 seconds upon compressor start
The ICC will cause the compressor to be energized for 30 seconds minimum run
time except when TEST button is pushed without a Y1 call
Call for Operation (Y2 Call)
5 sec delay from Y1 to Y2
1 minute recycle when Y2 call ends
The control will not allow the 2 stage solenoid to be energized for 1 minute after
the solenoid has been deenergized.
3-minute Anti-short Cycle Timer
The ICC has a built in 3-minute time delay between compressor operations to
protect the compressor against short cycling (Status flashing c).
The 3-minute time delay can be bypassed when a Y1 call is present by pressing
the TEST button for 1 second and releasing (Status solid on c).
30 Second Minimum Run Timer
The ICC has a built in 30 second minimum unit run time (Status flashing c).
1 Second Compressor/Fan Delay
The ICC starts/stops the outdoor fan 1 second after the start/stop of the compres-
sor upon a Y1 call to minimize current inrush and/or voltage droop.
Low Pressure Control (LPC)
Upon a Y1 call, if the ICC senses an open LPC it will not allow the compressor to
be energized (diagnostic code 21).